Schneider TM241CE40T | logic controller, Modicon M241, 40 IO, transistor, PNP, Ethernet

Thông số kỹ thuật
Range of produc
Modicon M241
Product or component type
Logic controller
[Us] rated supply voltage
24 V DC
Discrete input number
24, discrete input 8 fast input conforming to IEC 61131-2 Type 1
Discrete output type
Transistor
Discrete output number
16 transistor 4 fast output
Discrete output voltage
24 V DC for transistor output
Discrete output current
0.1 A for fast output (PTO mode) (Q0...Q3)
0.5 A for transistor output (Q0...Q15)
Complementary
Discrete I/O number
40
Maximum number of I/O expansion module
7 (local I/O-Architecture)
14 (remote I/O-Architecture)
Supply voltage limits
20.4…28.8 V
Inrush current
50 A
Power consumption in W
32.6…40.4 W (with max number of I/O expansion module)
Discrete input logic
Sink or source
Discrete input voltage
24 V
discrete input voltage type
DC
Voltage state 1 guaranteed
>= 15 V for input
Voltage state 0 guaranteed
<= 5 V for input
Discrete input current
10.7 mA for fast input
7 mA for input
Input impedance
4.7 kOhm for input
2.81 kOhm for fast input
Response time
<= 2 µs turn-on, I0...I7 terminal(s) for fast input
<= 2 µs turn-off, I0...I7 terminal(s) for fast input
<= 2 µs turn-on, Q0...Q3 terminal(s) for fast output
<= 2 µs turn-off, Q0...Q3 terminal(s) for fast output
50 µs turn-on, I0...I15 terminal(s) for input
50 µs turn-off, I0...I15 terminal(s) for input
<= 34 µs turn-on, Q0...Q15 terminal(s) for output
<= 250 µs turn-off, Q0...Q15 terminal(s) for output
Configurable filtering time
1 µs for fast input
12 ms for fast input
0 ms for input
1 ms for input
4 ms for input
12 ms for input
discrete output logic
Positive logic (source)
Output voltage limits
30 V DC
Maximum current per output common
2 A
Maximum output frequency
20 kHz for fast output (PWM mode)
100 kHz for fast output (PLS mode)
1 kHz for output
Accuracy
+/- 0.1 % at 0.02…0.1 kHz for fast output
+/- 1 % at 0.1…1 kHz for fast output
Maximum leakage current
5 µA for output
Maximum voltage drop
<1 V
Maximum tungsten load
<2.4 W
Protection type
Short-circuit protection
Short-circuit and overload protection with automatic reset
Reverse polarity protection for fast output
Reset time
10 ms automatic reset output
12 s automatic reset fast output
Memory capacity
64 MB for system memory RAM
Data backed up
128 MB built-in flash memory for backup of user programs
Data storage equipment
<= 16 GB SD card (optional)
Battery type
BR2032 lithium non-rechargeable, battery life: 4 year(s)
Backup time
2 years at 25 °C
Execution time for 1 KInstruction
0.3 ms for event and periodic task
0.7 ms for other instruction
Application structure
3 cyclic master tasks + 1 freewheeling task
8 external event tasks
4 cyclic master tasks
8 event tasks
Realtime clock
With
Clock drift
<= 60 s/month at 25 °C
Positioning functions
PTO function 4 channel(s) (positioning frequency: 100 kHz)
PTO function 4 channel(s) for transistor output (positioning frequency: 1 kHz)
Counting input number
4 fast input (HSC mode) at 200 kHz
16 standard input at 1 kHz
Control signal type
A/B at 100 kHz for fast input (HSC mode)
Pulse/direction at 200 kHz for fast input (HSC mode)
Single phase at 200 kHz for fast input (HSC mode)
Integrated connection type
Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface
Non isolated serial link serial 2 with removable screw terminal block connector and RS485 interface
USB port with mini B USB 2.0 connector
Ethernet with RJ45 connector
Supply
(Serial 1)serial link supply: 5 V, <200 mA
Transmission rate
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
480 Mbit/s for bus length of 3 m for USB
10/100 Mbit/s for Ethernet
Communication port protocol
Non isolated serial link: Modbus master/slave
Port Ethernet
10BASE-T/100BASE-TX - 1 port(s) copper cable
ethernet services
FDR
DHCP server via TM4 Ethernet switch network module
DHCP client embedded Ethernet port
SMS notifications
Updating firmware
SNMP client/server
Programming
NGVL
Monitoring
IEC VAR ACCESS
FTP client/server
Downloading
SQL client
Modbus TCP client I/O scanner
Ethernet/IP originator I/O scanner embedded Ethernet port
Ethernet/IP target, Modbus TCP server and Modbus TCP slave
Send and receive email from the controller based on TCP/UDP library
Web server (WebVisu & XWeb system)
OPC UA server
DNS client
Local signalling
1 LED (green) for PWR
1 LED (green) for RUN
1 LED (red) for module error (ERR)
1 LED (red) for I/O error (I/O)
1 LED (green) for SD card access (SD)
1 LED (red) for BAT
1 LED (green) for SL1
1 LED (green) for SL2
1 LED (red) for bus fault on TM4 (TM4)
1 LED per channel (green) for I/O state
1 LED (green) for Ethernet port activity
Electrical connection
Removable screw terminal blockfor inputs and outputs (pitch 5.08 mm)
removable screw terminal blockfor connecting the 24 V DC power supply (pitch 5.08 mm)
Maximum cable distance between devices
Unshielded cable: <50 m for input
Shielded cable: <10 m for fast input
Unshielded cable: <50 m for output
Shielded cable: <3 m for fast output
Insulation
Between supply and internal logic at 500 V AC
Non-insulated between supply and ground
Between input and internal logic at 500 V AC
Non-insulated between inputs
Between fast input and internal logic at 500 V AC
Between output and internal logic at 500 V AC
Non-insulated between outputs
Between fast output and internal logic at 500 V AC
Between output groups at 500 V AC
Marking
CE
Surge withstand
1 kV power lines (DC) common mode conforming to IEC 61000-4-5
1 kV shielded cable common mode conforming to IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to IEC 61000-4-5
1 kV relay output differential mode conforming to IEC 61000-4-5
1 kV input common mode conforming to IEC 61000-4-5
1 kV transistor output common mode conforming to IEC 61000-4-5
Web services
Web server
Maximum number of connections
8 Modbus server
8 SoMachine protocol
10 web server
4 FTP server
16 Ethernet/IP target
8 Modbus client
Number of slave
64 Modbus TCP:
16 EtherNet/IP:
Cycle time
10 ms 16 EtherNet/IP
64 ms 64 Modbus TCP
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
height
90 mm
Depth
95 mm
Width
190 mm
Net weight
0.62 kg

Thông tin tham khảo:
  • Upload chương trình PLC Schneider M221 về máy tính

  • Upload chương trình PLC Schneider Modicon M340

  • Kết nối online chương trình PLC Schneider Motion Lexium LMC10, LMC20

  • Kết nối PLC, HMI, Biến tần Schneider với nhau


  • Truyền thông Modbus PLC với Biến tần Siemens S7-1200 vs Schneider ATV312




Đăng nhận xét Blogger

 
Top